DESCRIPTION
The MMX-7 input module can be addressed with an encoder on site, occupying an address in a loop of the controller. When the monitoring module receives the closing signal of the switch, it transmits the signal to the controller through the bus.
characteristic
• Built-in model identification system, the control panel can automatically identify the device as MMX-7
• Direct circuit power supply, no need for additional power cord power supply • SEMS screws with clips for easy wiring
• Decimal address setting (101-199), encoder setting
• LED flashes during normal operation, and always on when alarming
parameter
-Working temperature: -10 ℃ ~ 60 ℃
-Working humidity: 5% ~ 95% RH, no condensation
-Communication line terminals 1, 2
Working voltage: 15 ~ 32VDC
Working current: maximum 85μA @ 24VDC
Large 1.8mA24V (red light lock)
Loop resistance: maximum 40Ω
-The external power supply requires one terminal 3 and 4 voltage: 18 ~ 29VDC (filtering, shaping and power limitation)
Ripple: Max 100mVRMS
Current: 102mA / module
-Initial circuit equipment (IDC) -Terminal 5, 6 current: maximum 102mA IDC circuit resistance: maximum 25Ω
Quiescent current: Max 12mA @ Max IDC
Voltage matching detector current: maximum 2.4mA
Alarm current: maximum 18mA
Type: Type B (classB)
Termination resistance: 3.9kΩ